Call us now
08045479103
Technical Specifications
Input Voltage Range : 300 - 460V / 340 - 480V / 360 - 460V AC 3 Ph
Output Voltage (3 Ph) : 415V AC
System : Unbalanced 4 wire: R Y B N
Connections : Star
Operating Frequency : 47 to 53 Hz
Output Voltage Adjustable : 380 to 415V AC in 3 Ph
Output Voltage Regulation : + 1% (No Load)
Output Voltage Regulation : + 1% (Full Load)
Overload Capacity : 120%
Correction Rate : 60 / 30 / 25V per Sec-3 Phase
Waveform Distortion : Nil
Output Waveform : True Reproduction of Input
Insulation : Class F
Short Circuit period & Percentage : 300% for 250 Milli Sec. 0 0
Normal Operation Temperature : 0 C to 45 C 0
Climate Conditions : 90% Rh Max. Non Condensing at 35 C
Type of Cooling : Natural air cooled up to 600 KVA
Mode of system : Fully Automatic
System Construction : As per IS : 9815 – 1994
Salient Features
Quick response time 10 milli sec (half a cycle)
Very high efficiency above 98%
Excellent regulation as high as +/- 0.5%
Micro controller†controlled system
Wide input range of operations & high speed of correction
Metering On LCD Display
3ph Input voltage ph to ph and ph to Neutral
3ph Output voltage ph to ph and ph to Neutral
System Frequency
Output Current on each ph
Protections
Single Phasing Prevention
Output Electronic Over Load Protection
Phase Reversal Protection
Input Short Circuit Protection with MCB
Input Over Load Protection with MCB
Output Low Voltage Protection
Output High Voltage Protection
Audio Alarm for Protections
Indications
Mains Input on 3 LED Indications,
3ph output on indication
Phase Reversal indication
over Load indication
Indications in LCD Display
Input High and Input low
Output on indication
Output high Cutoff and Output Low Cutoff
Programmable Parameters
Output voltage set ( 210-245V)
Output Low Voltage Cutoff
Output High Voltage Cutoff
Input Low on LCD Display
Input High on LCD Display
Sensitivity / Regulation
Over Load Cutoff
CT full scale